An effective water treatment programme will control corrosion, scale formation and fouling, as well as legionella and other microbial activity.
B & V Chemicals can offer a corrosion coupon analysis and certificate service, using the expertise of our in-house laboratory services. The analysis of corrosion through using corrosion coupons is recommended by the Health and Safety Executive (HSE) in their Approved Code of Practise L8 and accompanying Technical Guidance; HSG274 (section 1.34)
While on-site water analysis can provide you with some information about corrosion activity, it does not provide the full story. Corrosion coupons, however, a much more accurate, longer term corrosion rate, which is representative of the whole system. The result is better informed, more accurate water treatment programme. Corrosion coupon monitoring, particularly of critical and large closed circuit systems, is also recommended in BSRIA BG50.
This service is available for all common metals of mild steel, stainless steel 316 and 304, copper, brass and aluminium. Other metals may be available on request.
The guidelines for acceptable corrosion levels in systems composed of different metal types can be found in the table below. Using corrosion coupons will allow water treatment professionals to demonstrate that the water treatment programme in place on site in a cooling tower or closed circuit is actually proving effective in minimising corrosion.
Metal | Rate | Description |
Mild steel | <1 | Excellent corrosion control |
1 -2 | Good corrosion control | |
2 - 5 | "Warning" look for control in system | |
>5 | High corrosion rate | |
Galvanised | Not relevant | |
Aluminium (remember to consider pitting) | <1 | Excellent corrosion control |
1 -2 | Good corrosion control | |
2 - 5 | "Warning" look for control or issues in the system | |
2 - 5 | High corrosion rate | |
Copper | <0.1 | Excellent corrosion control |
0.1-0.4 | Good corrosion control | |
0.5-1.0 | "Warning" look for control in system | |
<1.0 | High corrosion rate | |
Brass | <0.1 | Excellent corrosion control |
0.1-0.4 | Good corrosion control | |
0.5-1.0 | "Warning" look for control in system | |
<1.0 | High corrosion rate | |
Stainless steel | <0.1 | Excellent corrosion control |
0.1-0.4 | Good corrosion control | |
0.5-1.0 | "Warning" look for control in system | |
<1.0 | High corrosion rate |
Our technical support team are on hand to discuss your requirements and find the most appropriate solution for your water system whatever your water treatment requirements.
Contact us on ownlabel@bvwater.co.uk.